TECHNICAL SPECIFICATIONS OF HOT AIR GENERATOR
1. |
Model | AIRPACK-400. | AIRPACK-2500. |
2. |
Construction | Rectangular | Cylindrical |
2 |
Capacity | 4,00,000 Kcal/hr. | 25,00,000 Kcal/hr. |
3 |
Type | Indirect Fired. | Indirect Fired. |
6 |
Outlet Temp. of Air. | Upto 200 Deg.C (Max. upto 350 Deg. C) | Upto 200 Deg.C (Max. upto 350 Deg. C) |
5 |
Air Flow Rate. | 9412 kg/hr (for 200 Deg.C. Outlet Temp.). | 58823 kg/hr (for 200 Deg.C. Outlet Temp.). |
6 |
Pressure Drop Across Hot Air Generator. | 200-250 mm WC. | 200-250 mm WC. |
7 |
No. of Flue Gas Passes. | 4 | 4 |
8 |
Fuel | LDO/HSD. | LDO/HSD. |
9 |
Calorific Value of Fuel on GCV | ||
| a) F.O. | 10300 kcal/kg. | 10300 kcal/kg. | |
| b) LDO | 10880 kcal/kg | 10880 kcal/kg | |
| c) HSD | 10960 kcal/kg. | 10960 kcal/kg. | |
| Calorific Value of Fuel on NCV | |||
| a) F.O. | 9710 kcal/kg. | 9710 kcal/kg. | |
| b) LDO | 10210 kcal/kg. | 10210 kcal/kg. | |
| c) HSD | 10280 kcal/kg | 10280 kcal/kg | |
10 |
Efficiency on NCV. | 93% + 1% | 93% + 1% |
11 |
Fuel Oil Consumption (93% Eff.on NCV). | ||
| a) F.O. | 44.29 kg/hr. | 276.84 kg/hr. | |
| b) LDO | 42.12 kg/hr. | 263.28 kg/hr. | |
| c) HSD | 41.83 kg/hr. | 261.49 kg/hr. | |
12 |
Connected
Load a) Combustion Blower and Fuel Pump. |
3.3 kW. |
9.7 kW. |
13 |
Burner Modulation. | ON-OFF. | STEPLESS |
14 |
Overall Dimensions (Uninsulated). | ||
| a) Length. | 2200 mm | 9000 mm | |
| b) Width | 1200 mm | 3600 mm | |
| c) Height | 2800 mm | 4000 mm | |
15 |
Dead Weight (Approx.). | 1800 kg. | 11000 kg. |
| Note : The pressure drop across Hot Air Generator is specified as a Estimated value. The figure may very for different outlet temp.And ambient condition. | |||